Energy Efficiency Standard for Social Housing: peer review

Peer review scrutinising the example dwellings in the Energy Efficiency Standard for Social Housing consultation document.


Appendix D - Pre- & Post-2002 Specs

Example Group H Performance Parameters

The period of construction describing example group H bridges two RdSAP age bands; I (1999-2002), and J (2003-2007). The reason for this split in the RdSAP age bands is due to changes in the buildings standards, most significantly the 6 th amendment which came into force from 4 th March 2002. This saw not only the application of more onerous U-values for external constructions, but a difference in the values relative to the fuel type and efficiency of the system. As a result, many of the default RdSAP assumptions demonstrate very different performance parameters.

The tables below summarise the performance parameters associated with the default RdSAP assumptions, example dwelling specifications, minimum Building Standards in place at the beginning of the example group H construction period, and the changes which came into force halfway through.

Walls - Table 1 summarises the wall U-values determined by the default RdSAP assumptions for a number of Scottish construction types, as well as the original and updated U-value criteria applicable to new constructions. The wall U-values are in compliance with the Building Standards corresponding to the earlier time period, relative to age band I. The latter half of the construction period, relative to RdSAP age band J, are subject to more onerous U-values.

Table 1 Example group H wall U-values

Period U-value
RdSAP
Age Band I (1999-2002) 0.45 W/m 2.K*

0.40 W/m 2.K**
Age Band J (2003-2007) 0.30 W/m 2.K*

0.30 W/m 2.K**
4 th amendment to the Technical Standards (1997) (in force from 29/12/97)
SAP rating =< 60 0.45 W/m 2.K
SAP rating > 60 0.45 W/m 2.K
6 th amendment to the Technical Standards (2001) (in force from 04/03/02)
Gas boiler efficiency >=78% 0.30 W/m 2.K
Electric heating or gas boiler with efficiency <78% 0.27 W/m 2.K
* Based on 'cavity as built' or 'system build as built' ** Based on 'timber frame as built'

Floor - Table 2 summarises the floor U-values determined by the default RdSAP assumptions and calculation methodology. It can be seen that the floor U-values for example dwellings 22 and 23, are in compliance for the earlier period of the timeframe corresponding to age band I.

Table 2 Example group H floor U-values

RdSAP
Period U-value
Age Band I (1999-2002) Solid ground floor, 50mm all-over floor insulation Example dwelling 22: 0.26 W/m 2.K

Example dwelling 23: 0.33 W/m 2.K
Age Band J (2003-2007) Solid ground floor, 75mm all-over floor insulation Example dwelling 22: 0.22 W/m 2.K

Example dwelling 23: 0.26 W/m 2.K
4 th amendment to the Technical Standards (1997) (in force from 29/12/97)
SAP rating =< 60 0.35 W/m 2.K
SAP rating > 60 0.45 W/m 2.K
6 th amendment to the Technical Standards (2001) (in force from 04/03/02)
Gas boiler efficiency >=78% 0.25 W/m 2.K
Electric heating of gas boiler with efficiency <78% 0.22 W/m 2.K

Roof - Table 3 shows the U-values for the various criteria assuming a pitched roof with insulation between joists. The specification for the example dwelling roof insulation is 200mm. Based on this assumption, new dwellings completed between 1999 to the beginning of 2002 would meet compliance, however as of the 6 th amendment to the Building Standards an increase in the loft insulation thickness would be necessary.

Table 3 Example group H roof U-values

RdSAP
Period U-value
Age Band I (1999-2002) 150mm insulation 0.26 W/m 2.K
Age Band J (2003-2007) 250mm insulation 0.16 W/m 2.K
Specified thickness of 200mm insulation 0.20 W/m 2.K
4 th amendment to the Technical Standards (1997) (in force from 29/12/97)
SAP rating =< 60 0.20 W/m 2.K
SAP rating > 60 0.25 W/m 2.K
6 th amendment to the Technical Standards (2001) (in force from 04/03/02)
Gas boiler efficiency >=78% 0.16 W/m 2.K
Electric heating of gas boiler with efficiency <78% 0.16 W/m 2.K

Windows - Table 4 details the RdSAP window U-value assumptions and the minimum building standards applicable to the construction period from 1999 to 2007. The specification for example group H baseline glazing is 'post-2003', however the RdSAP data for glazing installed before 2003 is also provided for reference.

It can be seen that specification of 'post-2003' standards ensures that the majority of the example dwellings meet compliance with the more recent buildings standards, however the properties featuring electric heating require an even lower U-value, of 1.8 W/m 2.K. It would be expected that properties constructed in the earlier half of the example group H timeframe, up to 2002, would have a poorer U-value than the assumed 2.0 W/m 2.K.

Table 4 Example group H window U-values

RdSAP
Period U-value
Double glazed unit, Scotland, before 2003 3.1 W/m 2.K
Double glazed unit, Scotland, 2003 or later 2.0 W/m 2.K
4 th amendment to the Technical Standards (1997) (in force from 29/12/97)
SAP rating =< 60 3.0 W/m 2.K
SAP rating > 60 3.3 W/m 2.K
6 th amendment to the Technical Standards (2001) (in force from 04/03/02)
Gas boiler efficiency >=78% 2.0 W/m 2.K
Electric heating of gas boiler with efficiency <78% 1.8 W/m 2.K